Q: Mokonzi na ngai ya transformateur ya test ya 50 kV / 5 kVA - alobi "kangisa yango kaka na câble ya 3 km." Eloko moko ayokaka mabe. Nazali na ntina?
A: OZALI NA RAISON. KOSALA BOYE TE. Oyo ezali erreur #1 ya débutant oyo ebebisaka ba transformateurs.
Mokakatano #1: Surcharge ya monene
• Nsinga ya 3 km ya 35 kV: C ≈ 0,5 μF. Na_futaka=50,000 × 314 × 0,5×10−6=7.85 A.
• Nguya oyo esengeli: 50 kV × 7,85 A=393 kVA.
• Transformateur na yo ezali na 5 kVA. Ozali kosenga puissance nominale ya 78×. Enroulement ekobimisa milinga na ba secondes.
Mokakatano #2: Bobebisi ya forme ya mbonge
• Charge capacitive → facteur ya puissance ya liboso → noyau ya transformateur e saturar.
• Forme d’onde ya sortie ekomi sommet - facteur ya crête emati de 1.414 à 1.6–1.8.
• Momekano ya RMS ya 50 kV ekoki kobimisa 90 kV ya sommet - ya koleka ndelo oyo ekangami te.
Mokakatano #3: Régulation ya tension elongi te
• Na charge te, otie 50 kV.
• Tango câble ekangami, tension ekiti na 10–20 kV (transformateur ekoki kopesa courant te).
• Kotombola entrée → TX e saturar mingi → tension epanzani → fusible ezo souffler.
Tango nini transformateur ya test ekoki kosala pona ba câbles?
|
Câble na 35 kV |
C |
Courant @ 50 kV |
OK pona 5 kVA TX? |
|
< 100 m |
< 15 nF |
< 0.24 A |
❌ Encore 2,4× surcharge |
|
< 50 m |
< 8 nF |
< 0.12 A |
❌ 1,2× koleka ndelo |
|
< 20 m |
< 3 nF |
< 0.05 A |
✅ Na kati ya cote |
Mobeko ya makasi: Salelá kaka transformateur ya test mpo na ba câbles oyo ezali mokuse koleka ~25 mètres. Mpo na eloko nyonso oyo eleki molai, salelá système résonant série.
Buku ya kopona nokinoki
|
Soki osali test... |
Kopona... |
Ntina |
|
CT, PT, bushing, barre ya bus ya mokuse |
Komekatransformateur oyo ezali na kati |
Simple, ya talo moke, puissance ekoki |
|
Biloko ya kobongola / 1–2 ba baies SIG |
Komekatransformateur oyo ezali na katito SR ya moke |
Bango mibale basalaka |
|
Câble ya distribution < 500 m |
SR ya moke (30–60 kV) . |
Esengeli Q-facteur ya économie ya puissance |
|
Câble HV > 1 km |
SR (100–300 kV) Ezali na . |
Kaka option viable |
|
Stator ya générateur |
SR (20–30 kV ya likolo I) . |
Forme d'onde propre, courant ya likolo |
|
Test induite na transformateur |
SR na > 100 Hz |
Fréquence > classé esengeli |
|
Routine ya usine (charge moko) . |
Meka TX to SR fixe |
Pona oyo esalemi na ndenge ya standard |
|
Momekano ya bilanga (mikumba ekeseni) . |
SR ya modulaire |
Flexibilité ya ko reconfigurer |